600RZW
Return to Product Page
- Kohler Co. provides one-source responsibility for the generating system and accessories.
- The generator set and its components are prototype-tested, factory-built ,and production-tested.
- The generator set complies with ISO 8528-5, Class G4, requirements for transient performance.
- A one-year limited warranty covers all systems and components. Two-, five-, and ten-year extended warranties are also available.
Alternator features:
- The brushless, rotating-field alternator has broad range reconnectability.
- The pilot-excited, permanent-magnet (PM) alternator provides superior short-circuit capability.
- NEMA MG1 ,IEEE, and ANSI standards compliance for temperature rise and motor starting.
- Sustained short-circuit current of up to 300% of the rated current for up to 10 seconds.
- Sustained short-circuit current enabling down stream circuit breakers to trip without collapsing the alternator field.
- Self-ventilated and dripproof construction.
- Digital solid-state, volts-per-hertz voltage regulator with ±0.25% no-load to full-load regulation.
- Brushless alternator with brushless pilot exciter for excellent load response.
Other features:
- The low coolant level shutdown prevents overheating (standard on radiator models only).
- The generator set is direct-mounted to the skid.
- An electronic, isochronous governor delivers precise frequency regulation.
- Electronic engine controls manage the engine.
- Lean-burn natural gas technology provides maximum power and fuel efficiency.
- Rich-burn natural gas technology reduces harmful exhaust emissions when used with a catalytic converter.
| Prime Ratings: |
504 kW (630 kVa) |
| Standby Ratings: |
528 kW (660 kVa) |
| Hertz: |
50 Hz |
| Alternator Type: |
Brushless, Permanent-Magnet, Pilot Exciter |
| Engine Manufacturer: |
Waukesha |
| Engine Model: |
VGF L36GSID |
| Cylinder Arrangement: |
12 V |
| Max Power at Rated RPM: |
548 kWm (735 BHP) |
| Prime Fuel Consumption at |
|
| 100% load: |
152 m³/hr (5364 cfh) |
| 75% load: |
120 m³/hr (4228 cfh) |
| 50% load: |
88 m³/hr (3092 cfh) |
| 25% load: |
55 m³/hr (1956 cfh) |
| Standby Fuel Consumption at |
|
| 100% load: |
165 m³/hr (5819 cfh) |
| 75% load: |
129 m³/hr (4569 cfh) |
| 50% load: |
94 m³/hr (3319 cfh) |
| 25% load: |
59 m³/hr (2070 cfh) |
|
|